CyberPower ST425 vs EC850LCD: Watts, Battery Outlets and Desk Fit

CyberPower ST425 Standby UPSModel ST425CyberPower EC850LCD Ecologic UPSModel EC850LCD

The CyberPower EC850LCD supplies six battery-backed outlets and is rated 510 W. The ST425 supplies four and is rated 260 W. The EC850LCD adds six surge-only outlets, three with USB-linked ECO controls. Measure the equipment’s load and count the outlets that need battery backup before choosing.

Choose by what matters to you

Choose CyberPower ST425 Standby UPS ST425

Choose the ST425 when your measured connected load is within 260 W, four battery-backed outlets cover the equipment that must stay on during an outage, and the manufacturer runtime information for your load meets your intended shutdown window. Its manufacturer sheet gives only model-relative half-load and full-load points, so do not assume those are your system's runtime.

Check price on Amazon

Choose CyberPower EC850LCD Ecologic UPS EC850LCD

Choose the EC850LCD when the measured load is above 260 W but no more than its 510 W rating, or when you need up to six battery-backed outlets, an LCD readout, or USB-linked ECO control for peripherals on the surge-only ECO outlets. Check runtime at your own watt draw; its 7.9-minute half-load point is at 255 W versus the ST425's 130 W half-load point, not a same-load comparison.

Check price on Amazon

If your measured load exceeds 510 W, you need a shutdown window that neither manufacturer's load-specific information supports, or the devices that must ride through an outage need more than six backed outlets, look for a different capacity or outlet arrangement. Do not plug outage-critical equipment into the EC850LCD's surge-only ECO outlets. Before buying either model, check the 120 V grounded outlet location, right-angle plug clearance, five-foot cord path and the unit's stated dimensions against the shelf or desk space.

As an Amazon Associate I earn from qualifying purchases.Affiliate disclosure

Products compared

CyberPower ST425 Standby UPS · ST425

CyberPower

CyberPower ST425 Standby UPS

CyberPower’s ST425 is a standby UPS rated at 425 VA / 260 W. It has four battery-and-surge outlets plus four surge-only outlets, a U.S. 120 V NEMA 5-15P input with a five-foot cord, and an 8.3 × 4.5 × 3.2-inch footprint. Its published runtime points are six minutes at this model’s half load and 1.5 minutes at full load; check runtime at your actual equipment draw rather than treating either point as your forecast.

Model ST425
Amazon ASIN B07GZR981Y

Check current price on Amazon
CyberPower EC850LCD Ecologic UPS · EC850LCD

CyberPower

CyberPower EC850LCD Ecologic UPS

The U.S. 120 V/NEMA CyberPower EC850LCD is rated at 850 VA / 510 W, with six battery-and-surge outlets and six surge-only outlets, three ECO-controlled. It has a multifunction LCD, USB-dependent ECO behavior and a 12.2 × 3.1 × 7-inch footprint. Its published runtime points are 7.9 minutes at this model’s half load and 2.3 minutes at full load; check load-specific runtime for your equipment.

Model EC850LCD
Amazon ASIN B00DBAA696

Check current price on Amazon

Differences that matter

Difference
CyberPower ST425 Standby UPS
CyberPower EC850LCD Ecologic UPS
Why it matters
Rated output and runtime points
CyberPower ST425 Standby UPSST425: 425 VA / 260 W; manufacturer lists 6 minutes at half load (130 W) and 1.5 minutes at full load (260 W).
CyberPower EC850LCD Ecologic UPSEC850LCD: 850 VA / 510 W; manufacturer lists 7.9 minutes at half load (255 W) and 2.3 minutes at full load (510 W).
Use the watt rating as a first load-fit screen, then consult the chosen model's load-specific runtime information for the actual connected draw. The two half-load points are at 130 W and 255 W, so the quoted minutes cannot show which unit runs longer at the same load.
Sources for Rated output and runtime points
Battery-backed vs surge-only outlet count
CyberPower ST425 Standby UPS8 total NEMA 5-15R outlets: 4 battery-and-surge protected and 4 surge-only.
CyberPower EC850LCD Ecologic UPS12 total NEMA 5-15R outlets: 6 battery-and-surge protected and 6 surge-only; 3 of the surge-only outlets are ECO-controlled.
Count only devices that must remain powered in an outage when deciding whether the available backed outlets are enough. The EC850LCD's larger total includes surge-only connections; ECO-controlled outlets are not battery-backed.
Sources for Battery-backed vs surge-only outlet count
Readout and ECO workflow
CyberPower ST425 Standby UPSThe ST425 data sheet lists a power-on LED indicator; it does not document an LCD or ECO-controlled outlets.
CyberPower EC850LCD Ecologic UPSThe EC850LCD brochure lists a multifunction LCD and three ECO-controlled surge-only outlets. USB connection is required for the described automatic shutoff when the computer is off or asleep.
Pick the EC850LCD if the documented readout or USB-linked peripheral-control routine suits your setup. Keep equipment that must stay on during an outage on its battery-backed outlets, not on the surge-only ECO bank. The ST425 sheet's silence is not proof that no other feature exists.
Sources for Readout and ECO workflow
Plug, cord and physical placement
CyberPower ST425 Standby UPS120 VAC NEMA 5-15P right-angle 45°-offset input plug, 5-ft cord; 8.3 × 4.5 × 3.2 in (W × H × D).
CyberPower EC850LCD Ecologic UPS120 VAC NEMA 5-15P right-angle 45°-offset input plug, 5-ft cord; 12.2 × 3.1 × 7 in (W × H × D).
Both require a compatible 120 V outlet and have the same stated cord length and plug style, while the EC850LCD occupies a longer/larger footprint. Measure the shelf and check that the angled plug and cord route leave enough clearance; the listed dimensions are product measurements, not required installation clearances.
Sources for Plug, cord and physical placement

Size the load before comparing minutes

Start with the measured watts of the equipment you plan to connect. The ST425 is rated 425 VA / 260 W; the EC850LCD is rated 850 VA / 510 W. The watt figure is the useful first screen for whether the load is within the manufacturer's rated output, while it does not by itself tell you how long the battery will support the system.

CyberPower lists 6 minutes at ST425's half load and 1.5 minutes at full load; its half-load point is 130 W. For EC850LCD, the brochure lists 7.9 minutes at half load and 2.3 minutes at full load; its half-load point is 255 W. Since these points use different watt draws, do not compare the minutes as if both UPS units powered the same load. Look for load-specific runtime information for your measured draw and shutdown target.

Allocate only battery-backed outlets to outage-critical devices

The ST425 has eight outlets: four combine battery backup and surge protection, and four are surge-only. The EC850LCD has twelve outlets: six battery-backed and six surge-only, including three ECO-controlled surge-only outlets. Count the devices that must remain on battery, not just total plugs, before deciding that you have enough connections.

EC850LCD's brochure describes an automatic ECO routine for peripherals connected to the ECO outlets when a computer is off or asleep, and says USB is required. These outlets are surge-only. Keep any device that must remain powered during an outage on the battery-backed group instead.

Check the outlet, cord path and footprint

Both manufacturer documents list a 120 VAC NEMA 5-15P input, a right-angle plug offset by 45 degrees and a five-foot cord. The ST425 is listed at 8.3 × 4.5 × 3.2 inches; EC850LCD at 12.2 × 3.1 × 7 inches. Measure the placement area and check the angled plug's clearance at your actual wall outlet or power location. The cord length does not guarantee that a particular desk layout works, and the product dimensions are not an installation-clearance figure.

Product details

CyberPower ST425 Standby UPS

Rated output
425 VA / 260 W Source
Outlet allocation
8 NEMA 5-15R outlets: 4 battery-and-surge protected, 4 surge-only Source
Runtime points (manufacturer rated-load conditions)
6 minutes at half load (130 W, half of 260 W) and 1.5 minutes at full load (260 W); not a runtime estimate for another load Source
Input and footprint
120 VAC NEMA 5-15P, right-angle 45°-offset plug, 5-ft cord; 8.3 × 4.5 × 3.2 in (W × H × D) Source

CyberPower EC850LCD Ecologic UPS

Rated output
850 VA / 510 W Source
Outlet allocation and ECO
12 NEMA 5-15R outlets: 6 battery-and-surge protected, 6 surge-only, of which 3 are ECO-controlled; USB is required for the documented automatic computer-off/sleep routine Source
Runtime points (manufacturer rated-load conditions)
7.9 minutes at half load (255 W, half of 510 W) and 2.3 minutes at full load (510 W); not a runtime estimate for another load Source
Input and footprint
120 VAC NEMA 5-15P, right-angle 45°-offset plug, 5-ft cord; 12.2 × 3.1 × 7 in (W × H × D) Source

Before you buy

  • Measure the connected equipment's watt draw instead of choosing from VA alone. Treat 260 W and 510 W as the manufacturers' rated-output ceilings, not recommendations for a specific setup.
  • Count how many devices actually need battery backup. ST425 has four backed outlets; EC850LCD has six. The latter's three ECO-controlled outlets are surge-only.
  • If you want the EC850LCD ECO behavior, plan for its required USB connection and connect only suitable peripherals to that surge-only bank; do not use it for devices that must remain on during an outage.
  • Runtime numbers are model-relative: half load is 130 W on ST425 and 255 W on EC850LCD. Check the exact model's runtime data at your actual load rather than comparing 6 vs 7.9 minutes as an equal-load result.
  • Check a grounded 120 V NEMA 5-15 outlet, five-foot cord route, angled-plug clearance and the exact body dimensions against the desk, shelf or cabinet. No UPS performance or backup duration is guaranteed by this comparison.

Community discussions

A new owner asked about grounded plug fit

CyberPower ST425 Standby UPS

One new ST425 owner asked why some grounded-plug openings seemed blocked and whether charging might change the fit. The post is an unresolved question; it does not establish a defect, cause or fix.

What to check

Check the exact ST425 outlet diagram and manual against the plugs and outlet positions your equipment needs. This post does not show that charging changes outlet fit.

Original Reddit discussion

Common questions

Does the EC850LCD last longer than the ST425 at the same load?

The cited manufacturer sheets do not establish that. Their half-load points are 7.9 minutes at 255 W for EC850LCD and 6 minutes at 130 W for ST425; full-load points are also at different watt draws. Check load-specific information for the model and actual wattage you plan to connect.ST425 Standby UPS System — Data SheetEC850LCD Ecologic UPS — Manufacturer Brochure and Specifications

How many outlets provide battery backup?

The ST425 has four battery-and-surge outlets and four surge-only outlets. EC850LCD has six battery-and-surge outlets and six surge-only outlets, three of the surge-only outlets being ECO-controlled.ST425 Standby UPS System — Data SheetEC850LCD Ecologic UPS — Manufacturer Brochure and Specifications

Do the EC850LCD ECO outlets provide battery backup?

No. CyberPower's brochure identifies them as ECO-controlled surge-only outlets. The described automatic peripheral shutoff requires a USB connection and responds to a connected computer being off or asleep. Reserve the six battery-backed outlets for equipment that must stay powered during an outage.EC850LCD Ecologic UPS — Manufacturer Brochure and Specifications

Will either UPS fit behind or under my desk?

Compare the listed product dimensions and allow room for its 45-degree-offset plug and five-foot cord route. ST425 is listed at 8.3 × 4.5 × 3.2 inches; EC850LCD at 12.2 × 3.1 × 7 inches. These figures do not include an additional clearance requirement, so check the actual shelf and outlet layout.ST425 Standby UPS System — Data SheetEC850LCD Ecologic UPS — Manufacturer Brochure and Specifications

Sources and scope

The listed runtimes use different watt loads for the two models. Check the current runtime chart for your measured load and count the battery-backed outlets separately from the surge-only bank.

  1. ST425 Standby UPS System — Data Sheet
  2. EC850LCD Ecologic UPS — Manufacturer Brochure and Specifications